CL1001-CL1002
Conductivity level controls for liquids
The CL1001 and CL1002 instruments are electrical conductivity level controls whose working is founded on measuring the resistance between two or more electrodes dip into fluids under control. Liquid between a reference electrode and one or more level electrodes causes the output relay to switchover.
Typical employments as level controls in tanks, boilers, deep wells and other containers, as alarm devices to detect flooding, presence or absence of water, and ice accumulation control.
It is possible to delay the relays devices for 5 seconds so that the turbulence of fluids does not cause unwanted switching (mod. CL1001-R5).
This instrument is built into a plastic case with an undecal connection.
Depending on the employment, various types of probes are available.
Typical employments as level controls in tanks, boilers, deep wells and other containers, as alarm devices to detect flooding, presence or absence of water, and ice accumulation control.
It is possible to delay the relays devices for 5 seconds so that the turbulence of fluids does not cause unwanted switching (mod. CL1001-R5).
This instrument is built into a plastic case with an undecal connection.
Depending on the employment, various types of probes are available.
Versions:
• CL 1001.1 - CL 1002.1 with power supply 110/220 Vac
• CL 1001.2 - CL 1002.2 with power supply 24 Vac
• CL 1001.1 - CL 1002.1 with power supply 110/220 Vac
• CL 1001.2 - CL 1002.2 with power supply 24 Vac
1. Undecal coupling
EMC
2014/30/EU
Absorbtion
2 VA
Adjustable sensitivity
2÷40kOhm
CL1001 output
relay 1 switch - 220Vac / 5A
CL1002 output
relay 2 switches NC 220 Vac / 5A
Low tension - LVD
2014/35/UE
Plastic case with undecal coupling
76x38x70mm
Power supply
110/220 Vac, 24 Vac ±15%, 50/60Hz
Protection degree
IP 40
Relative humidity
10÷90%
Voltage between electrodes
12 VAC
Working temperature
-20÷60°C